KP1000 Series Digital Program Controllers Download PS Sheet

Models KP1000 series are high-function digital program controllers. Being incorporated with high-performance microprocessors, they have materialized such high accuracies as +/- 0.1% of the indicating accuracy and 0.1 second of the controlling cycle. The controllers enable optimum program control to be performed over the wide temperature range. Since altogether sixteen kinds; viz, eight kinds that can optionally select the PID constants obtained by automatic tuning function step by step, and another eight kinds to be automatically selected by SV values, can be built-in.
They are standard-equipped with versatile functions such as multi setting, multi-range input, color LCD digital display and interactive system setting by full dot matrix color LCD.
  KP1000
Features Models Measuring Ranges Specifications

Input signals

Thermocouples B, R, S, K, E, J, T, WWRe5-26, WWRe0-26, Ni-NiMo, AuFe-Cr, N, PR5-20, PR20-40, Platinel, U, L
DC voltage

±10mV, ±20mV, ±50mV, ±100mV, ±5V

DC current

±20mA

Resistance thermometers

Pt100, JPt100, Pt50, Pt-Co

Accuracy rating ± 0.1% of input span ± 1 digit or 10µV, whichever is larger
(With thermocouple inputs, reference junction temperature compensation accuracy is not included.)
Reference temperature compensation accuracy

±0.5°C

Sampling period About 0.1 second
Burnout Upscale burnout for thermocouple and mV inputs
Output at burnout Optional set value: between -5% and 105% of control output
At burnout High alarm activation
Scaling DC voltage and DC current inputs: Optional scaling within 4 digits
Displays 1st display part: 7-segment back-lit LCD
2nd display part: Full dot-matrix (96 x 20 dots) back-lit LCD
Adjustable angle of viewing (± 20 degrees)
Power supply 85 to 264VAC, 50/60Hz (universal power supply)
Ambient temperature -10 to 50°C
Ambient humidity Less than 90%RH (no dew condensation)
Power consumption 100VAC maximum 15VA, 200VAC maximum 20VA
Weight About 750g (about 900g for models with full options)
Program pattern setting system Key switch setting
Number of program pattern steps Maximum 19 steps/pattern
Number of program patterns Maximum 19 patterns
Number of program pattern repetitions Maximum 9999 times
Number of program step repetitions Maximum 99 times
Parameters to be selected for each step PID constants (8 types, SV section automatic switching), Alarm (8 types x 4 points), Output limiter (high and low limits, 8 types), Output variation limit (8 types), Actual temperature compensation (8 types), Waiting time alarm (8 types), Sensor compensation (8 types), Time signals (total 10 types: 8 types, all OFF and all ON)
Control switching cycle About 0.1 second
Control system Current output type PID, On-off pulse type PID, SSR drive pulse type PID, On-off servo type PID, Voltage output type PID (option)
Auto tuning Provided. PID constants can also be set manually.
PID constants Settings for each of 8 set values are possible.
P: 0 to 999.9% (0 for on/off control)
I: 0 to 9999 seconds (0 for without reset action)
D: 0 to 9999 seconds
Anti-reset windup Setting of reset action: High 0 to 50.0%, Low (-) 50 to 0%
Current output type PID Output signal: 4 to 20mADC
Load resistance: Less than 750ohm
On-off pulse type PID Output signal On-off pulse conductive signal
Contact capacity Resistive load: 100VAC less than 2A, 200VAC less than 1A
Inductive load: 100VAC less than 1A, 200VAC less than 0.5A
Minimum load: more than 5VDC 10mA
Alarm points On-off pulse period Variable between about 1 to 180 seconds
SSR drive pulse PID Output signal On-Off pulse voltage signal
ON: 12VDC ± 10% (maximum 20mA)
OFF: Less than 0.6VDC
On-off pulse period Variable between about 1 to 180 seconds
Contact protective element Not built-in (sold separately)
On-off servo type PID Output signal On-off servo conductive signal
Contact capacity Inductive load: 100VAC 1A, 200VAC 0.5A
Feedback resistance 100ohmto 2kohm
Load current Standard: Maximum 1A, minimum 20mA
Light load: Maximum 2mA, minimum ImA
Alarm points 4 points for each control set point
Alarm system High/low alarms and deviation/absolute-value alarms
With standby function, independent setting for each set value.
Alarm outputs Transistor open-collector output (maximum load 24VDC, 50mA)
Communications interface RS-232C, RS-422A (option)
CE (option) EN61326 + A1 Class A, EN61000-3-2 + A14
EN61000-3-3, EN61010-1 + A2