Input Specifications |
|
Input signal |
|
Thermocouple… |
K, N, J, E, Platinel
II |
Resistance thermometer…Pt100,
JPt100 |
|
Accuracy rating |
Thermocouple input … ±0.3% of input span ±
1 digit or ±2°C, whichever is larger Resistance
thermometer input … ±0.2% of input span ± 1
digit |
|
Measuring unit |
°C or °F |
|
Sampling cycle |
About 0.25 second |
|
Burnout |
Up scale |
|
Allowable signal source
resistance |
Thermocouple inut…100
or lower Resistance thermometer input…10
or lower per wire |
|
Input shift |
-100.0 to
100.0°C |
|
Control Specifications |
|
Control cycle time |
Approx. 0.25 second |
|
Control system |
PID (2-position control is
available. |
|
Control setpoint |
2 sets switching, 4-digit
setting |
|
Auto-tuning |
Standard (Manual setting of PID constants
enabled) |
|
PID constants |
|
P… |
0 to maximum value
of range |
|
I… |
0 to 3600
seconds |
|
D… |
1 to 3600
seconds | |
|
Control gap |
0.1 to 100.0°C (2-position control
only) |
|
Anti-reset windup |
Automatic |
|
Output specifications |
On-off pulse type
|
|
Output
signal |
… |
On-off
pulse conductive signal |
|
|
Contact
ratings |
… |
Resistive
load: |
250VAC
3A |
|
|
|
|
Inductive
load: |
250VAC
1A |
|
|
Pulse
cycle |
… |
Approx. 1
second to 120 seconds
adjustable |
Current output type
|
|
Output
signal |
… |
4 to
20mADC |
|
|
Load
resistance |
… |
550
or less |
SSR drive pulse type
|
|
Output
signal |
… |
On-off
pulse voltage signal At ON 12VDC ± (0 to +2V)
maximum 40mA |
|
|
Pulse
cycle |
… |
Approx. 1
second to 120 seconds
adjustable | |
|
Alarm Specifications |
|
Alarm point |
1 point |
|
Temperature alarm type |
Deviation high alarm, deviation low
alarm Absolute value deviation high alarm,
absolute value deviation low alarm Deviation
high alarm with standby function Deviation low
alarm with standby function Absolute value
deviation high alarm with standby
function Absolute value deviation low alarm
with standby function Absolute value high
alarm, absolute value low alarm Absolute value
high alarm with standby function Absolute value
low alarm with standby function |
|
Loop break alarm |
Alarm activation when the control output is
maximum or minimum and the process value does not
vary more than a set band in a set time. Heater
disconnection, sensor disconnection, control
equipment failure Alarm time setting range: 0
to 200 minutes Alarm band: 0 to150°C or 0.0 to
150.0°C |
|
Alarm deadband |
0.1 to 100°C |
|
Alarm output |
Open collector 24VDC 0.1A
(maximum) |
|
Display Specifications |
|
Display |
4-digit LED |
|
Display contents |
PV or SV switching, Parameter
item |
|
General Specifications |
|
Power voltage |
100V to 240VAC 50/60Hz universal power
supply |
|
Working temperature range |
-10 to 50°C |
|
Working humidity range |
35 to 85%RH (no dew
condensation) |
|
Power consumption |
Maximum about 5VA |
|
installation |
Panel installation |
|
Weight |
About 100g |