Input Specifications |
|
Input signal |
|
Thermocouple… |
Standard universal:
B, R, S, N, K, E, J, T, U, L High temperature
universal: B, R, S, N, K, WRe5-WRe26, W-WRe26,
PtRh40-PtRh20, Platinel
II |
Resistance thermometer…Pt100,
JPt100 DC voltage…0 to 5V A 250
shunt resistor (sold separately) and the 5V (1 to
5V) are used. |
|
Accuracy rating |
±0.25% ± 1 digit (at reference operation
conditions) |
|
Reference junction compensation
accuracy |
±1.0°C (23°C±10°C), ±2.0°C (-10°C to
50°C) |
|
Measuring unit |
°C or °F |
|
Sampling cycle |
About 0.5 second |
|
Burnout |
Up scale (thermocouple input, resistance
thermometer input) |
|
Measuring current |
Resistance thermometer … 110µA |
|
Scaling |
Ranges/scales of DC voltage/current input
are optional settings. (-1999 to
9999) |
|
Scale decimal point |
0 to 3 |
|
Control Specifications |
|
Control cycle time |
Approx. 0.5 second |
|
Control system |
On-off pulse type PID system Current
output type PID system SSR drive pulse type PID
system Voltage output type PID system *
2-position control is selectable. |
|
Control setpoint |
2 sets switching, 4-digit
setting |
|
Setpoint ramp function: |
Setpoint ramp unit …°C/minute (common to
rising/falling) Setpoint rising ramp: 0 to 9999
(0 = no operation) Setpoint falling ramp: 0 to
9999 (0 = no operation) PV start function …At
SV change, power-on, Run/Ready |
|
Auto-tuning |
Standard (Manual setting of PID constants
enabled) |
|
PID constants |
|
P… |
0.1 (0.0) to 999.9%
(0 = 2-position) |
|
I… |
0 to 9999
seconds |
|
D… |
0 to 9999
seconds | |
|
PID deadband (gap) |
0.0 to 9.9% |
|
Anti-reset windup |
High limit … 0.0 to 100.0%, Low limit …
-100.0 to 0.0% |
|
Overshoot suppression function |
On/off selectable |
|
Control operation |
With direct/reverse action
switching |
|
Output specifications |
On-off pulse type
|
|
Output
signal |
… |
On-off
pulse conductive signal |
|
|
Contact
ratings |
… |
Resistive
load: |
100VAC 3A, 240VAC
3A, 30VDC 3A |
|
|
|
|
Inductive
load: |
100VAC 1.5A, 240VAC
1.5A, 30VDC 1.5A |
|
|
Pulse
cycle |
… |
Approx. 1
second to 180 seconds
adjustable |
Current output type
|
|
Output
signal |
… |
4 to
20mADC |
|
|
Load
resistance |
… |
600
or less |
SSR drive pulse type
|
|
Output
signal |
… |
On-off
pulse voltage signal At ON 12VDC ± 20% (load
current … 20mA or less) At OFF 0.8VDC or
less |
|
|
Pulse
cycle |
… |
Approx. 1
second to 180 seconds
adjustable |
Voltage output type
|
|
Output
signal |
… |
0 to
10VDC |
|
|
Output
resistance |
… |
Approx.
10 |
|
|
Load
resistance |
… |
50k
or
more | |
|
General Specifications |
|
Rated power voltage |
100V to 240VAC 50/60Hz universal power
supply |
|
Allowable power voltage |
90 to 264VAC |
|
Working temperature range |
-10 to 50°C (maximum 40°C at closed
installation) |
|
Working humidity range |
20 to 90%RH (no dew
condensation) |
|
Power consumption |
Maximum about 10VA |
|
Installation |
Panel installation |
|
Weight |
Maximum 200g |
|
International Standards |
|
CE |
EN61326 + A1 Class A, EN61000-3-2 +
A14 EN61000-3-3,EN61010-1 + A2 |
|
UL |
UL3111-1 |
|
CSA (C-UL) |
C22.2 No. 1010 |
|
IP |
NEMA4X (IP66) (front
protection) |
|