LT450, 470 Series Digital Indicating Controllers Download PS Sheet

High function type with 5-digit display of measured value
New overshoot suppression function "JyroNavi"

Models LT450 and LT470 digital indicating controllers feature all functions, which are necessary for various control applications, including newly developed PID algorithms and a learning type overshoot suppression function "JyroNavi".
  LT450/LT470
Features Models Measuring Ranges Specifications
Input Specifications
Input signal
Thermocouple… B, R, S, N, K, E, J, T, U, L, WRe5-WRe26, W-WRe26, PtRh40-PtRh20, Platinel II
Resistance thermometer…Pt100, JPt100
DC voltage…0 to 20mV, 0 to 5V, 0 to 10V
DC current…4 to 20mADC
A 250ohm shunt resistor (sold separately) and the 5V (1 to 5V) are used.
Accuracy rating ±0.1% ± 1 digit (at reference operation conditions)
Exception: ±0.3% ± 1 digit for PtRh40-PtRh20
Reference junction compensation accuracy ±1.0°C (23°C±10°C), ±2.0°C (-10°C to 50°C)
Measuring unit °C or °F
Sampling cycle About 0.2 second
Burnout Up scale/down scale (selectable)
Scaling Ranges/scales of DC voltage/current input are optional settings.
(-19999 to 20000)
Scale decimal point 0 to 4
Control Specifications
Control cycle time Approx. 0.2 second
Control system On-off pulse type PID system
Current output type PID system
SSR drive pulse type PID system
On-off servo type PID system
Voltage output type PID system
Multiple control type (on-off pulse type/current output type/SSR drive pulse type) PID system
* 2-position control is selectable.
Auto-tuning Standard (Manual setting of PID constants enabled)
PID constants 4 sets switching (interlocking to SV)
P…  0.1 (0.0) to 999.9% (0 = 2-position)
I…  0 to 9999 seconds
D…  0 to 9999 seconds
PID deadband (gap) 0.0 to 9.9% (4 sets switching, interlocking to SV)
Anti-reset windup High limit … 0.0 to 100.0%, Low limit … -100.0 to 0.0%
Overshoot suppression function On/off selectable (4 sets independent switching, interlocking to SV, independent keeping of learned results)
Control operation With direct/reverse action switching
Output specifications
  • On-off pulse type
       Output signal …  On-off pulse conductive signal
       Contact ratings …  Resistive load: 100VAC 5A, 240VAC 5A, 30VDC 5A
          Inductive load: 100VAC 2.5A, 240VAC 2.5A, 30VDC 2.5A
      Pulse cycle …  Approx. 1 second to 180 seconds adjustable

  • Current output type
       Output signal …  4 to 20mADC
       Load resistance …  600ohm or less

  • SSR drive pulse type
       Output signal …  On-off pulse voltage signal
    At ON 12VDC ± 20% (load current … 20mA or less)
    At OFF 0.8VDC or less
       Pulse cycle …  Approx. 1 second to 180 seconds adjustable

  • On-off servo type
       Output signal …  On-off conductive signal
       Feedback resistance …  100ohm to 2.5kohm
      Contact ratings …  Resistive load: 100VAC 5A, 240VAC 5A, 30VDC 5A
        …  Inductive load: 100VAC 2.5A, 240VAC 2.5A, 30VDC 2.5A
          Minimum load 5VDC or more, 10mADC or more

  • Voltage output type
       Output signal …  0 to 10VDC
       Output resistance …  Approx. 10ohm
       Load resistance …  50kohm or more
  • General Specifications
    Rated power voltage 100V to 240VAC 50/60Hz universal power supply
    Allowable power voltage 90 to 264VAC
    Working temperature range -10 to 50°C (maximum 40°C at closed installation)
    Working humidity range 20 to 90%RH (no dew condensation)
    Power consumption Maximum about 16VA
    Installation Panel installation
    Weight About 250 to 350g (LT450)
    About 350 to 500g (LT470)
    International Standards
    CE EN61326 + A1 Class A, EN61000-3-2 + A14
    EN61000-3-3, EN61010-1 + A2
    UL UL3111-1
    CSA (C-UL) C22.2 No. 1010
    IP NEMA4X (IP66) (front protection)