Input Specifications |
|
Input
signals |
Thermocouples |
B, R, S, N, K, E,
J, T |
| Resistance
thermometers |
Pt100 |
| DC
voltage |
0 to 5V |
| DC
current |
4/20mA [By using a
250 shunt resistor
(sold separately) and 5V range (1/5V)] |
| Measuring range |
Refer to the list of measuring ranges. |
| Accuracy ratings |
±0.3%
of measuring range ± 1 digit (at reference operation conditions) |
| Reference junction compensation accuracy |
±1.0°C (23°C ± 10°C), ±2.0°C (-10°C to
50°C) |
|
Sampling period |
Approx. 0.5 second |
| Burnout |
Up scale (T/C input, RTD input) |
| Allowable signal source resistance |
Thermocouples |
200 or less |
| Voltage
input |
1K or less |
| Resistance
thermometers |
10 or less (per
wire) * Resistance of 3 wires needs to be equal. |
| Input resistance |
T/C, DC voltage: 1M or more |
| Measuring current |
RTD: Approx. 125uA |
Measuring input shift
(sensor correction) |
Can be set by the resolution being 0.1 times the setting resolution of SV (-1999
to 9999) |
| Digital filter |
0.0 to 99.9 seconds |
| Scaling |
Range/scale of DC voltage/current input (-1999 to 9999), optional setting |
| Scale decimal point |
0 to 3 |
| Maximum allowable input range |
DC voltage: -5V/+8V DC |
| Resistance
thermometers: ±5VDC |
| Maximum common mode voltage |
30VAC |
| Common mode rejection ratio (T/C input) |
130dB or more (50/60Hz) (signal source resistance 1 or less) |
| Series mode rejection ratio (T/C input) |
50dB or more (50/60Hz) (signal source resistance 1 or less) |
|
Control Specifications |
| Control cycle time |
Approx. 0.5 seconds |
| Control system |
On-off pulse type PID system
SSR drive type PID system |
| Control set point |
1 set point. 4-digit setting. |
| Set point limiter |
Within measuring range |
| Set point ramp function |
Set point
ramp unit |
°C/minute
(common to rising/falling) |
| Set point
rising ramp |
0 to 9999 (0=no operation) |
| Set point
falling ramp |
0 to 9999 (0=no operation) |
| PV start
function |
At SV change, power-on, changing from Ready
to Run |
| Control set point accuracy ratings |
Relative error to displayed value: ±1 digit |
| Auto-tuning |
Standard (Manual setting of PID constants
enabled) |
| PID
constants |
|
P: |
0.1 to 999.9% |
|
I: |
0 to 9999 seconds |
|
D: |
0 to 9999 seconds |
|
| PID
deadband (gap) |
0.0 to 9.9% |
| Anti-reset windup |
High limit |
0.0 to 100.0% |
|
Low limit |
-100.0 to 0.0% |
| Overshoot suppression function |
ON/OFF selectable |
| Control operation |
With direct/reverse action switching |
|
Output Specifications |
| On-off pulse type |
| Output signal |
On-off pulse conductive signal (relay "a" contact output) |
| Contact ratings |
Resistive load: 100VAC 3A, 240VAC 3A, 30VDC 3A
Inductive load 100VAC 1.5A, 240VAC 1.5A, 30VDC 1.5A |
| Electrical relay life |
More than 100,000 times |
| Pulse cycle |
Approx. 1 second to
180 seconds adjustable (1 second increments) |
| Contact protection element |
Not built-in [If required, add a contact protection element (sold
separately) externally.] |
|
| SSR drive pulse type |
| Output signal |
On-off pulse voltage signal
- At ON: 12VDC ±20% (load current 20mA or less)
- At OFF: 0.8VDC or less |
| Pulse cycle |
Approx. 1 second to
180 seconds adjustable (1 second increments) |
|
| Output limiter |
1 set
High limit: 0.0 to 105.0% Low limit: -5.0 to 100.0% |
| Output variation limiter |
0.1 to 100.0% |
| Output preset |
-100.0 to 100.0% |
| Run/Ready |
Run/Ready (control stop, output: control
output value at Ready) switchable |
| Control output at Ready |
-5.0 to 105.0% |
| Control at power recover |
Continuous/Ready switchable |
|
Event Specifications |
| Event calculation |
2 points |
| Event output point |
None (standard)
2-points relay output (EV1/EV2) can be added as an option. |
| Event type |
Setting to each of Event 1/2
Absolute value alarm High/Low, standby enable/disable
Deviation alarm High/low/high & low, standby enable/disable, FAIL, heater
disconnection alarm (option) |
| Event set point |
Event 1/2 individual setting |
| Event dead band |
Can be set by the resolution
being 0.1 times the setting resolution of SV, Setting to each Event 1/2 |
| Event output phase |
Normal/reverse switchable |
| Event output at Ready |
Off/computation switchable |
|
Display Specifications |
| Display type |
4-digit seven-segment LED
display, two lines
Status display 5 independent LEDs |
| Display content |
|
First LED (green display) |
At operation mode: Measured
value (PV)
At setting mode: Parameter item |
|
Second LED (red display) |
At operation mode: Setpoint (SV)
At setting mode: Parameter |
|
Status LED (red/green) |
AT(green): Blinks during the
auto-tuning is executed.
OUT1 (green): Lights when the control output 1 (heating) is output
OUT2 (green): Lights when the control output 2 (heating) is output
EV1 (red): Lights when event1 is active
EV2 (red): Lights when event2 is active |
|
| Automatic return |
Return to operation mode if any
key is not pressed for more than 3 minute in setting mode. |
| Key lock |
Locking function of parameters,
4 levels |