The BR series, new graphic recorders for
the next generation, fit various applications in industrial fields to
test/research fields. The measured data are displayed on a 5.5" TFT color LCD
display, stored into the internal flash memory and can be saved to a 3.5" floppy
disk. You can convert electronic data to a popular spreadsheet software by using
the optional software [PASS].
The MODBUS
communications link to computer systems makes the configuration with your
personal computer easy. The recorders need no consumable costs including chart
papers and inks used in conventional recorders. |
 |
 |
|
Options
|
Specifications
|
Remote
contacts/
alarm output |
Remote
Contacts |
The
following operations are available by contact input (4 points) and common
(2 points) signal. (parameter connection)
| (1) |
Data memory trigger
When the conduct
signal is changed to ON from OFF, the data storage into the internal memory
starts. |
| (2) |
Data memory signal
During ON of the
conduct signal, the data is stored into the internal memory |
| (3) |
Message display
When the conduct
signal is changed to ON from OFF, pre-registered message is displayed. |
| (4) |
Totalizing reset
Reset of the totalizing
data (All channels together) |
|
Alarm
Output |
Independent
output at alarm activation: 6 points
| Contact
rating |
MOS relay output |
240V(AC,DC) 50mA
resistive load |
| Mechanical
relay output* |
100VAC 0.5A resistive
load |
| 240VAC 0.2A resistive
load |
| 100VDC 0.3A resistive
load |
* Not conforming to
CE-marking, UL and CSA (C-UL) |
|
Communications |
RS-232C,
RS-422A or RS-485 (to be specified)
MODBUS protocol
(RTU/ASCII)
Functions: Data
transmission, Parameter programming, Operation, Data communications input |
|
2-port
communications |
For
a host computer: Refer to the above
For low-order
communications: By connecting with CHINO's instruments, treats the data
from the instruments as the data communications input.
Low-order communications:
RS-422A or RS-485
(to be specified)
Instruments:
Recorders - BR1000,
AL3000, AH3000
Controllers -
DZ1000, DZ2000
MODBUS protocol |
|
Mathematics |
The
following math functions can be applied to the measured data. The math
functions can be also applied to the calculated data.
(1) Arithmetic,
(2) Square root, (3) Logarithm, Natural logarithm,(4) Exponential, (5)
Maximum, minimum, average, (6) Temperature/humidity |
|
Totalize |
Totalizing
measured data or calculated data
| (1) |
Interval: 1 minute
to 24 hours or no interval |
| (2) |
Start time: 0
hour 1 minute to 23 hours 59 minutes |
|
|
Daily
report file |
Creates
a daily report file by specifying channels, time (optional time, max. 24
points) and the following items.
(1)Instant vale,
(2) Maximum value in block, (3) Minimum value in block, (4) Average value
in block, (5) Maximum value in day, (6) Minimum value in day, (7) Average
value in day |
|
Shunt
resistor for current input |
For
measuring current by adding 250
or 20  |
|
 |
|